LH-ZJD直(zhi)流(liu)接地(di)故障(zhang)探(tan)測(ce)儀(yi)
咨(zi)詢(xun)電(dian)話:13524730762
LH-ZJD直(zhi)流(liu)接地(di)故障(zhang)探(tan)測(ce)儀(yi)
產品(pin)概(gai)述:
直(zhi)流(liu)系(xi)統(tong)接地(di)是壹(yi)種(zhong)易(yi)發生且對電(dian)力(li)系(xi)統(tong)危害較大的(de)故(gu)障(zhang)。直(zhi)流(liu)系(xi)統(tong)正(zheng)極(ji)接地(di),可能造成(cheng)繼電(dian)保(bao)護誤(wu)動(dong),因(yin)為跳閘線(xian)圈(quan)接直(zhi)流(liu)電(dian)源負(fu)極,系(xi)統(tong)再有(you)壹(yi)點(dian)接地(di)或絕緣(yuan)不良(liang),可能(neng)引起保(bao)護誤(wu)動(dong);直(zhi)流(liu)系(xi)統(tong)負(fu)極接地(di),系統(tong)再有(you)壹(yi)點(dian)接地(di)或絕緣(yuan)不良(liang),可將(jiang)跳閘回路(lu)或(huo)合閘(zha)回路(lu)短路(lu),造成(cheng)保(bao)護拒(ju)動,此(ci)時(shi)系(xi)統(tong)發生故障(zhang),保(bao)護的(de)拒動(dong)必然導(dao)致系統(tong)事故擴大(da),同(tong)時(shi)還可能(neng)燒壞(huai)繼電(dian)器(qi)的觸點(dian)或燒保(bao)險。
LH-ZJD直(zhi)流(liu)接地(di)故障(zhang)探(tan)測(ce)儀(yi)重點(dian)解(jie)決了(le)直(zhi)流(liu)系(xi)統(tong)間接接地(di)、非金屬(shu)接地(di)、環路(lu)接地(di)、正(zheng)負(fu)同時(shi)接地(di)、正(zheng)負(fu)平(ping)衡(heng)接地(di)、多點(dian)接地(di)等疑難故(gu)障(zhang)的準(zhun)確(que)檢(jian)測,並(bing)且還能準確(que)的(de)顯(xian)示(shi)系統(tong)電(dian)壓、對地(di)電(dian)壓、接地(di)阻(zu)值,真(zhen)正(zheng)解(jie)決了(le)運(yun)行(xing)及檢修人(ren)員(yuan)的後(hou)顧之憂(you)。
產品(pin)特點(dian)
1.高(gao)精(jing)度(du)采樣鉗表
2.接地(di)點(dian)方向(xiang)顯(xian)示(shi)
3.具有(you)絕緣(yuan)指(zhi)數顯(xian)示(shi)功(gong)能
4.具有(you)波(bo)形(xing)顯(xian)示(shi)功(gong)能
5.操(cao)作簡(jian)單(dan),使(shi)用方便(bian)、快速
6.信號發生器(qi)與檢測(ce)器(qi)不受(shou)距離限(xian)制(zhi)
7.運行(xing)安全、可(ke)靠
技術參數
1. 可(ke)檢(jian)測(ce)接地(di)電(dian)阻(zu)範圍(wei)
系統(tong)電(dian)壓為220V時: 0 -500KΩ
系(xi)統(tong)電(dian)壓為110V時: 0 -250KΩ
系(xi)統(tong)電(dian)壓為48V時: 0 -50KΩ
系(xi)統(tong)電(dian)壓為24V時: 0 -10KΩ
2. 檢(jian)測(ce)信號功(gong)率(lv) ≤ 0.2W(信號發生器(qi)輸出功(gong)率(lv))
3. 抗(kang)對(dui)地(di)分布(bu)電(dian)容值:
對(dui)地(di)電(dian)容單(dan)支(zhi)路(lu)≤8uF,系(xi)統(tong)對地(di)總電(dian)容≤100uF;
4. 適用(yong)直(zhi)流(liu)系(xi)統(tong)電(dian)壓:
220V±10%,110V±10%,48V±10%,24V±10%,或用戶提出其它(ta)電(dian)壓等級(ji);
5. 環境溫度(du):-35℃~+55℃;
6. 相(xiang)對濕(shi)度(du):≤95%