MDDQ接地故障(zhang)探(tan)測儀
咨(zi)詢電話:13524730762
MDDQ接地故障(zhang)探(tan)測儀
壹、概(gai) 述(shu)
直流系(xi)統(tong)接地是壹種(zhong)易(yi)發(fa)生(sheng)且(qie)對(dui)電力系(xi)統(tong)危(wei)害較大(da)的故障(zhang)。直流系(xi)統(tong)正(zheng)極接地,可(ke)能(neng)造(zao)成繼(ji)電保護誤(wu)動(dong),因(yin)為跳閘(zha)線(xian)圈接直流電源負(fu)極,系(xi)統(tong)再(zai)有壹點接地或(huo)絕(jue)緣不(bu)良,可(ke)能(neng)引(yin)起保(bao)護誤(wu)動(dong);直流系(xi)統(tong)負(fu)極接地,系(xi)統(tong)再(zai)有壹點接地或(huo)絕(jue)緣不(bu)良,可(ke)將(jiang)跳閘(zha)回路(lu)或(huo)合閘(zha)回路(lu)短路(lu),造成保護拒(ju)動(dong),此(ci)時系(xi)統(tong)發(fa)生(sheng)故障(zhang),保(bao)護的拒動(dong)必(bi)然導(dao)致(zhi)系(xi)統(tong)事(shi)故擴(kuo)大(da),同時還可(ke)能(neng)燒壞繼(ji)電器的觸點或(huo)燒保險。
我公司(si)自主(zhu)設計制(zhi)造的便(bian)攜式直流接地查(zha)找儀,能夠適用於任(ren)何電壓等(deng)級(ji)的直流系(xi)統(tong),配(pei)備了(le)高(gao)精度(du)的檢測鉗表,通(tong)過(guo)對(dui)多種(zhong)信(xin)號的高效(xiao)處理(li)大(da)大(da)提高(gao)了(le)檢測範(fan)圍與抗幹(gan)擾(rao)能(neng)力(li);采用了*計算(suan)方法和(he)模(mo)糊控制(zhi)理(li)論(lun),將被檢(jian)測支(zhi)路(lu)的絕(jue)緣程(cheng)度(du)以絕(jue)緣指數(shu)及(ji)波(bo)形的形式表示(shi)出(chu)來,充(chong)分(fen)體(ti)現(xian)了人(ren)工(gong)智能的*性(xing);對(dui)於(yu)接地點位(wei)置(zhi)的斷定(ding),它(ta)們更(geng)是(shi)擁有準確的判(pan)斷力(li),每次檢(jian)測都(dou)能夠指(zhi)出(chu)接地點位(wei)置(zhi)相對(dui)檢(jian)測點的方向(xiang),從(cong)而(er)快(kuai)速、準確地實現(xian)環(huan)路(lu)接地檢測。除(chu)此(ci)之外(wai),用戶可(ke)以根據自(zi)身(shen)系(xi)統(tong)需(xu)要在(zai)絕(jue)緣告(gao)警(jing)門(men)限(xian)值(zhi)範圍(wei)內訂制(zhi)合適的絕(jue)緣告(gao)警(jing)門(men)限(xian)值(zhi)的設備,用戶只(zhi)需要將(jiang)鉗表上(shang)的檔(dang)位與檢測器上(shang)的量程(cheng)對(dui)應起來就(jiu)能實(shi)現(xian)直流接地的檢測或(huo)者(zhe)是絕(jue)緣程(cheng)度(du)的分析(xi)。
此(ci)儀表不(bu)僅重點解決了直流系(xi)統(tong)間(jian)接接地、非(fei)金屬(shu)接地、環(huan)路(lu)接地、正(zheng)負(fu)同時接地、正(zheng)負(fu)平(ping)衡(heng)接地、多點接地、、等疑難故障(zhang)的準確檢測,並(bing)且(qie)還能準確的顯示(shi)系(xi)統(tong)電壓、對(dui)滴(di)電壓、接地阻(zu)值(zhi),,真正(zheng)解決了運(yun)行及(ji)檢修人(ren)員(yuan)的後顧之憂(you)。
本儀表以系(xi)統(tong)安(an)全為首(shou)要前提,按(an)行(xing)業標準的高要(yao)求(qiu),以可(ke)靠(kao)的低頻(pin)信(xin)號方式進(jin)行(xing)檢(jian)測,並(bing)在(zai)現(xian)場(chang)進(jin)行(xing)了(le)大(da)量的實際應用,對(dui)系(xi)統(tong)無(wu)任何影(ying)響。
MDDQ接地故障(zhang)探(tan)測儀
二. 儀表的構成
該儀表由信(xin)號發(fa)生(sheng)器、故障(zhang)檢(jian)測器和(he)信(xin)號采(cai)集(ji)器(鉗表)三部分(fen)組成,信(xin)號發(fa)生(sheng)器與直流系(xi)統(tong)正(zheng)負(fu)母(mu)線和(he)地相連,當直流系(xi)統(tong)出(chu)現(xian)接地故障(zhang)後(hou),它(ta)會(hui)自動(dong)產(chan)生(sheng)壹個(ge)低(di)頻(pin)小(xiao)信(xin)號,故障(zhang)檢(jian)測器與鉗表獨(du)立於信(xin)號發(fa)生(sheng)器,故障(zhang)檢(jian)測器與鉗表之間使(shi)用連接線(xian)相連,通(tong)過(guo)對(dui)待(dai)檢(jian)測支(zhi)路(lu)漏電流信(xin)號的采集(ji)、分析(xi),從(cong)而(er)判(pan)斷出(chu)該(gai)支(zhi)路(lu)的絕(jue)緣情(qing)況(kuang)。
三、儀表的工(gong)作原(yuan)理(li)
定位(wei)儀表的工(gong)作原(yuan)理(li)是:當直流系(xi)統(tong)發(fa)生(sheng)接地故障(zhang)或(huo)絕(jue)緣降低(di)(整(zheng)個(ge)直流系(xi)統(tong)絕(jue)緣電阻(zu)小(xiao)於報警(jing)整定(ding)值(zhi)),直流系(xi)統(tong)電壓監(jian)測儀表發出(chu)警(jing)報時,將信(xin)號發(fa)生(sheng)器接入(ru)直流系(xi)統(tong)的正(zheng)、負(fu)母(mu)線和(he)地之間。信(xin)號發(fa)生(sheng)器自(zi)動(dong)判(pan)斷直流系(xi)統(tong)電壓等(deng)級(ji),自動(dong)判(pan)斷接地故障(zhang)的極性(xing)、接地程(cheng)度(du),自(zi)動(dong)分(fen)析(xi)絕(jue)緣監測平(ping)衡(heng)電橋回路(lu)接線(xian)方式和(he)平(ping)衡(heng)電橋電阻(zu)大(da)小(xiao),形成信(xin)號輸(shu)出(chu)的智能反(fan)饋,向(xiang)直流正(zheng)負(fu)母(mu)線和(he)地間,發(fa)射適宜系(xi)統(tong)檢(jian)測,對(dui)系(xi)統(tong)無(wu)影(ying)響的低頻(pin)信(xin)號,並(bing)實(shi)時顯示(shi)系(xi)統(tong)電壓、正(zheng)對(dui)地電壓、負(fu)對(dui)地電壓和(he)系(xi)統(tong)對(dui)地絕(jue)緣總(zong)阻(zu)抗。
故障(zhang)檢(jian)測器檢(jian)測各(ge)回路(lu)對(dui)地絕(jue)緣的直流信(xin)號漏電流,並(bing)模(mo)擬(ni)顯(xian)示(shi)接地回路(lu)絕(jue)緣狀態,判(pan)斷出(chu)接地故障(zhang)回路(lu)(支(zhi)路(lu)),並(bing)繼(ji)續沿(yan)故障(zhang)回路(lu)(支(zhi)路(lu))檢測出(chu)接地故障(zhang),將(jiang)故障(zhang)點準確定位。
信(xin)號發(fa)生(sheng)器、故障(zhang)檢(jian)測器均采用微計算(suan)機技術,具(ju)有集(ji)成程(cheng)度(du)高(gao),判(pan)斷速度快(kuai),檢(jian)測靈敏(min)度高、抗幹(gan)擾(rao)能(neng)力(li)強、故障(zhang)定(ding)位(wei)準確等特點。在(zai)軟(ruan)件處理(li)上利(li)用了模(mo)糊控制(zhi)理(li)論(lun)和(he)通(tong)信(xin)的噪聲(sheng)理(li)論(lun),並(bing)依(yi)據直流系(xi)統(tong)的特點優(you)化(hua)了(le)算法,即(ji)使(shi)系(xi)統(tong)有大(da)分布(bu)電容(rong)的幹(gan)擾(rao)、電磁脈(mai)沖幹(gan)擾(rao)和(he)其(qi)它(ta)噪聲(sheng)幹(gan)擾(rao)的影(ying)響,也能準確地判(pan)斷出(chu)接地故障(zhang)點,為接地故障(zhang)的查(zha)找提供(gong)了(le)有力(li)的保障(zhang)。在(zai)硬(ying)件(jian)上(shang)引(yin)進(jin)*的檢測傳(chuan)感器,直流信(xin)號檢(jian)測靈敏(min)度高達0. 1mA,可(ke)檢(jian)測150K-500K接地的檢測靈敏(min)度,使(shi)多點接地、環(huan)路(lu)接地、絕(jue)緣普遍(bian)降低(di)等(deng)難以解決的問(wen)題迎(ying)刃而(er)解。